Practical Air Terminal Selection and Layout Procedure

Paper originally published in the ASHRAE Journal Here: https://www.nxtbook.com/nxtbooks/ashrae/ashraejournal_OKRFGH/index.php#/p/50

Practical Diffuser Selection and Layout Procedure

The selection and layout of diffusers to maximize occupant thermal comfort can be a complicated and time-consuming task. Given the sheer quantity of diffusers that must be selected and laid out on every project, developing a streamlined and consistent process can help firms remain profitable in a competitive environment. This paper intends to describe a practical selection and layout procedure that provides occupant comfort, minimizes construction cost, and can be applied to most spaces quickly and effectively.

Constraints:

No single procedure could encapsulate the engineering design required to adequately distribute air in any space that an architect can envision. There will always be edge cases and limitations. As such, we will work with the following constraints and assumptions:

1)The investigation will be limited to spaces where overhead air supply is possible. We won’t include, for example, gymnasiums, which typically require a large space between the court or field and the nearest overhead obstruction.
2)The focus will be on spaces designed primarily for human comfort. We won’t include, for example, surgery suites, where the primary intent of the air distribution system is to create an envelope of cold clean air around the staff and patient.
3)A consistent diffuser look will be maintained by assuming all diffusers in a space will be the same model. This will limit our coverage options, but a consistency is key when designing the aesthetics of a space.
4)The assumption will be made that windows don’t need “washing”. Historically, linear slot diffusers have been used to blow warm air onto windows in the winter, when the delta T across the window is highest, in an effort to keep the interior window surface temperature to within 18 °F of the space temperature to satisfy the allowable radiant temperature asymmetry in table 5.3.4.2 of ASHRAE 551. With the proliferation of the International Energy Code, washing is not as important because code minimum windows have high enough R-values that the internal surface temperature stays above the allowable temperature in the coldest regions of each climate zone. Table 1 shows the calculated window inside surface temperature for a select station in each climate zone assuming a 72 °F space temperature, 0.17 h·ft2·°F/Btu exterior air film resistance and a 0.68 h·ft2·°F/Btu interior air film resistance. Even if the project is a renovation with old single pane windows, “washing” windows with warm air is also tricky with a VAV system, you need the most throw when your VAV is at a minimum, instead consider fin tube heating under windows.
 
 
5)Diffusers will be selected and laid out based on the Comfort Criteria T50/L method where T50 is the diffuser throw length to a terminal velocity of 50 fpm and L is the characteristic Length of the space. This method is used to predict the level of comfort in a space by predicting its air distribution performance index (ADPI). A high ADPI indicates that a space will be well mixed, and a high percentage of occupants will be comfortable. Each diffuser type will have an ideal range of T50/L, provided by the diffuser manufacturer or by ASHRAE Applications chapter 572. Each space will have an actual T50/L, based on the dimensions of the space and the T50 of the selected diffuser. When selecting and placing diffusers, we will attempt to drive the actual T50/L as close as we can to the recommended T50/L. However, this paper will show that forcing the ideal and actual T50/L to match is unlikely.

.

The Characteristic Length, L:

The characteristic length is defined by ASHRAE Applications chapter 57 for perforated and louvered ceiling diffusers as the “Distance to wall or midplane between outlets”2. It is a single number for the entire space, so an effort must be made to keep all diffusers in a space equidistant from walls and other outlets. In order to accomplish this let’s look at a few examples. First, a square 20’x20’ space with one diffuser as shown in Figure 1A. If the diffuser is placed directly in the center of the space, the space has a characteristic length of 10’. If the characteristic length needs to be decreased, the diffusers should be placed in a 2×2 grid as shown in figure 1B.

Figure 1A: L= 10′       Figure 1B: L = 5′

With a non-square 20x40 rectangular space as shown in Figure 2, a single diffuser will not give a consistent characteristic length. The characteristic length in the direction of the 40’ wall is 20’, while the characteristic length in the direction of the 20’ wall is 10’. This deviation in the characteristic length has real-world implications. Depending on the throw of the selected diffuser air may crash against the 40’ wall and leave occupants along the 20’ wall with stagnant air. If a 1×2 grid of diffusers is utilized, as shown in Figure 3, the characteristic length becomes a consistent 10’. If the characteristic length needs decreased, the grid must increase to 2×4, as depicted in Figure 4. A mathematical definition of this pattern would be to create a grid of ATW x ATW * SR, where SR is the aspect ratio of the space and ATW is the grid count in the width (shorter) dimension, which can be increased in order to decrease the characteristic length.

.

Figure 2: L = 10’ and 20’.

.

Figure 3: L = 10’.

.

Figure 4: L = 5’.

.

In this 20’x40 space, the number of diffusers increased from 2 diffusers to 8 diffusers. This is a significant construction cost increase because in addition to the diffuser cost, additional flex duct, runouts, dampers, and taps are required.

.

While spaces come in various aspect ratios, diffusers can only be placed in discrete grids, i.e., 1×2, 2×4. Therefore, we must accept that characteristic lengths may deviate. For instance, consider a 20x25 space (Space Aspect Ratio, SR, =1.25) which would require 20 diffusers in a 4×5 grid (Diffuser Aspect Ratio, ATR=1.25) to achieve a consistent characteristic length of 2’ 6”. Figure 5 demonstrates how impractical this is. In addition to the cost of the diffusers, the design does not allow space for other ceiling devices such as lights, sprinkler heads, or occupancy sensors.

Figure 5: 4×5 diffuser pattern.

.

A 1×1 or 1×2 grid is much more reasonable for this space at the cost of having the characteristic length of the space slightly deviate (10’ vs 12’6” in the case of the 1×1 grid, and 6’3” vs 10’ in the case of a 1×2 grid, see Figure 6.

Figure 6: 1×1 and 1×2 diffuser pattern.

.

In addition to the space shape causing inconsistencies in the characteristic length, ceiling grids rarely line up perfectly with the space. It is also not uncommon for the ideal diffuser location to be taken by a higher priority ceiling element, such as a light. This causes the diffuser to shift even further, causing additional deviations to the characteristic length.

Because the characteristic lengths will vary slightly from diffuser to diffuser regardless, the constraint of keeping a perfectly consistent characteristic length can be relaxed and the ATW x ATW * SR layout grid can be improved by incrementally adding diffuser counts in the longer dimension using the following pseudocode algorithm:

SR = SL / SW

ATW = 1

ATL = ATW * [SR]   

ATR = ATL / ATW

Loop:

If |ATRSR| <= 0.5

  ATL = ATL + 1

    ATR = ATL / ATW

Else If |ATR – SR| > 0.5

  ATW = ATW + 1

ATL = ATW * [RS]

ATR = ATL / ATW

Until: desired diffuser count, ATW *ATL is reached

.

Where SR is the space aspect ratio, calculated by dividing the space length, SL, by the space width, SW, in this example it is assumed that SL is the larger dimension. ATR is the diffuser aspect ratio, calculated by dividing the diffuser count in the larger dimension, ATL, by ATW, which is the diffuser count along the shorter dimension. To ensure the diffuser grid follows the space shape as close as possible, initially and every time we add a diffuser in the shorter dimension, we multiply the grid count in the shorter dimension, ATW, by the rounded space aspect ratio, [SR]. When the diffuser aspect ratio diverges too significantly from the space aspect ratio, as indicated by the absolute value of the difference of the two aspect ratios being greater than 0.5 (|ATR – SR| > 0.5), then a diffuser in the shorter dimension must be added and the grid reset to match the space aspect ratio as close as possible.

..

This algorithm allows the user to add diffusers in the smallest increment possible while maintaining the tightest characteristic length. In the case of our 20’ x 40’ space, the diffuser counts would progress from 2 -> 3 -> 4 -> 4 -> 6 ->8 as shown in Figure 7.

Figure 7: Air Terminal layout pattern progression for the first 6 loops.

.

Length to 50 fpm Terminal Velocity, T50:

As previously mentioned, T50 is the diffuser throw length to a terminal velocity of 50 fpm. These values can be determined for a given diffuser size and throw pattern at a given CFM by reviewing the catalogue data. An example for a louvered face diffuser is given in Figure 83.

Figure 8: Typical diffuser catalogue data.

Regardless of what the ideal T50/L is, each diffuser is going to ideally “cover” some area for a given CFM based on the T50 throw of the diffuser. If the ideal T50/L is 1, then the area covered will be (T50*2 / 1)2, if the desired T50/L is 2, then the area covered is (T50*2 / 2)2. For an example from Figure 8, an 8” 4-way louvered face diffuser with 314 CFM of supply air would have a T50 throw of 14’ in all 4 directions, and with an ideal T50/L of 1, would cover a 28’x28’ area, or 784 s.f.

.

These areas are calculated for 6” and 8” in Table 2. If the coverage areas vs. the CFM across all neck sizes are plotted as shown in Figure 9, it is clear that the area “covered” by each diffuser is linear with the CFM applied. This holds true for many popular diffuser types, including radial plaque and perforated.

 

.

ad

Figure 9: Diffuser coverage area for popular models.

 

Because the coverage area decreases linearly with the CFM applied, even across multiple neck sizes, coverage area cannot be increased simply by adding more diffusers. If the diffuser count is increased from 1 to 4, the CFM available to assign each diffuser reduces by ¼ and the coverage area remains the same.

.

For example, assume 314 CFM is being delivered to a 20’x20’ space (0.785 CFM/s.f.), and a louvered face diffuser from Figure 8 with an ideal T50/L of 2 is used. If one 8” neck diffuser is placed in the center of the space, the characteristic length would be 10’ and the actual T50 would be 14, so the actual T50/L is 1.4 (14/10) which is only 70% (1.4/2) of the ideal 2. If the characteristic length is reduced to 5’ by placing four 6” neck diffusers, each diffuser would now only have 78.5 CFM and a 7’ throw. In this case, the actual T50/L is still 1.4 (7/5), and which is still 70% of the ideal 2, but now with more construction cost. Because the coverage area decreases linearly with the CFM applied, even across multiple neck sizes, this is true in all situations.

.

This demonstrates that with the given constraints, the actual T50/L is decided solely by the diffuser type and the airflow density (CFM/s.f.) of the space. With popular diffuser types and standard ranges of airflow densities at maximum flow, ideal T50/L ranges are typically met. It’s important to note, that while catalogue data is typically presented for isothermal conditions (i.e., supply air temperature equals room temperature), non-isothermal correction factors will only increase or decrease the slope of the coverage area vs. CFM lines, so the range of acceptable airflow densities will change in heating and cooling mode, but the conclusion is the same: adding more diffusers does not lead to better coverage.

.

As previously mentioned, with popular diffuser types and standard ranges of airflow densities at maximum flow, ideal T50/L ranges are typically met. However, at VAV minimum flow, the actual T50/L will typically be far below the ideal T50/L range. This is the situation that most engineers refer to as “dumping”, where there is not enough airflow coming out of the diffuser to cause adequate mixing and the air “dumps” onto the occupants, causing discomfort. While it may seem like “dumping” is a diffuser layout problem, it is a VAV minimum setpoint problem. Again, adding more diffusers does not alleviate the “dumping” problem because, for example, it is unclear if it is better to “dump” 40 CFM out of one 8” diffuser or 10 CFM out of four 6” diffusers.

.

To help accept the fact that the ideal T50/L will not be met at VAV minimum, consider a 2014 ASHRAE Research Project entitled “Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers” which showed that thermal comfort significantly improved when VAV minimums were reduced from 30% to 10% of maximum flow4, therefore the lower bound of the ideal T50/L ranges probably need to be reassessed.

.

Complex Spaces:

Complex spaces are a conglomerate of simple spaces. To address complex space, break them into simple rectangular subspaces and treat them separately.

.

Because architects are concerned about sight lights, complex spaces should be decomposed in a manner that leaves the largest area intact. For instance, the L shape space in figure 10 could be decomposed with a vertical line shown in the left image, or a horizontal line shown in the right image. The right image would have the largest consistent diffuser grid pattern and the most aesthetically pleasing sight lines, so it is the logical choice.

 

.

Figure 10: 2 ways of decomposing a space.

.

As shown in the previous section, coverage area decreases linearly with CFM, if more CFM is assigned to one subspace to attempt to get better coverage for that subspace, the other subspaces will be under covered. Therefore, CFM should be simply assigned to each subspace in proportion to its area.

.

There are some layouts in which uneven CFM distribution would be desired, for example, a lab space with many hot plates in a nook or a space with uninsulated brick and single pane glass walls.

.

Procedure:

Now that the individual components of the procedure have been addressed, we can formulate a streamlined and consistent process:

1)Select a diffuser manufacturer and model based on performance, material, aesthetics, cost, availability, and local support.
2)Determine an acceptable NC rating for the space and use the catalog to build a table of maximum allowable CFM for each neck size at the acceptable NC, such as the example in Figure 11.

Figure 11: An example table of the maximum allowable CFM.

3)Break complex spaces into rectangular subspaces leaving the largest continuous area intact.
4)Assign subspace airflow, CFMSS, to each subspace in proportion to the subspace’s area, SSA, to the total space area SA.
5)Decrease the characteristic length, by increasing the number of diffusers, following the procedure in the

Characteristic Length section of this paper.

6)Stop when the CFM/diffuser is below the allowable CFM of the largest neck size, CFMMax. Assign the smallest neck size where the maximum CFM for that neck size is above the CFM/diffuser.

As pseudocode:

For Each Subspace SS, in Space S

  CFMSS = CFMS * SSA / SA

SR = SL / SW

ATW = 1

ATL = ATW * [SR]

ATR = ATL / ATW

Loop:

  If CFMSS / (ATW *ATL) < CFMMax

  Break

If |RAT – Rs| <= 0.5

  ATL = ATL + 1

Else If |ATR – SR| > 0.5

  ATW = ATW + 1

ATL = ATW * [RS]

ATR = ATL / ATW

End  

The algorithm works well for many spaces, however the isovel method of diffuser layout cannot be totally disregarded. In some cases, ceiling spaces can be very cluttered due to other ceiling devices such as lighting, smoke detectors, and sprinkler heads which may take precedence, so the diffusers get pushed from their ideal location closer to the perimeter or an adjacent diffuser. This may require users to map the isovels to ensure air isn’t crashing on a wall or adjacent airstream at too high of a velocity, which could cause uncomfortable drafts in the occupied zone.

These rules don’t work well for long thin spaces, such as corridors, which may have aspect ratios of 10+. In this scenario, placing 10 diffusers down a hallway may not be worth it, two way throw patterns should be installed instead.

Additional Diffuser Suggestions:

1)Return diffusers should be placed diagonally to the supply grid to limit “short circuiting”, where the supply air is blown directly into a return. The same type of diffusers can be used for returns as well as supplies to ensure a consistent look and cadence of the ceiling.
2)Round neck diffusers with flexible duct connections should be used, as this greatly increases constructability because it allows slight adjustments to the diffuser location as the ceiling grid shifts from plan. The flexible duct also absorbs noise coming down the duct from fans and dampers. This also applies to return diffusers, even if they aren’t ducted. Return diffusers are frequent sources of “cross-talk” between private spaces like offices and adjacent public spaces. If too much noise is transferring back and forth, adding a short length of flexible duct to the returns is a quick and inexpensive way to mitigate the problem. Occasionally, there are also distracting visual elements in plenums, such as blinking lights from lighting controllers or glare from sheet metal, that can be hidden with a short length of flex duct attached to the round neck. If square neck diffusers are selected for returns, the fix becomes an expensive internally lined plenum box that may not fit in a crowded plenum.
3)A damper should be provided for every supply diffuser, preferably at the take-off from the main duct trunk. Dampers can produce significant noise3, by placing them as far away from the diffuser as possible, the ductwork and flexible duct connection can be used to dampen the noise generated by the damper.
4)Provide a lay-in frames for diffusers located in drywall ceilings. This allows the diffuser to be lifted for ceiling plenum space access which can facilitate balancing and general inspection.
5)Limit diffuser neck sizes to 12”. ASHRAE Fundamentals recommends at least one duct diameter of straight duct5 as shown in Figure 12. As the diffuser neck size increases, the required plenum space to properly install the diffuser grows as well.

Figure 12: Straight duct requirement

.

Conclusion:

Most designers and engineers follow the procedure outlined in this paper quickly and instinctively when laying out diffusers for most spaces. However, it is important to document our knowledge for new entrants to the industry and so that tools can be built to automate the more repetitive tasks.

References:

1.ASHRAE. 2016. “ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality”.
2.ASHRAE. 2015. “HVAC Applications Handbook”.
3.Titus 2015. “Product Catalogue”
4. Arens, Edward. Zhang, Hui. Hoyt, Tyler. Kaam, Soazig. Goins, John. Bauman, Fred. Zhai, Yongchao. Webster, Tom. West, Brandyn. Paliaga, Gwelen. Stein, Jeff. Seidl, Reinhard. Tullym, Braf. Rimmer, Jullian. Torftum, Jorn. 2014. “1515-RP Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers”
5.ASHRAE. 2021. “Fundamentals Handbook”.

.